Wattage Estimation Table - Kilowatt Hours to Heat Air

Amount of Air

Temperature Rise (F)

Air CFM   50   100   150   200   250   300   350   400   450   500   600
 100   1.7   3.3    5   6.7   8.3    10   11.7   13.3    15   16.7    20
 200   3.3   6.7   10   13.3   16.7    20   23.3   26.7    30   33.3    40
 300   5   10   15   20   25    30   35   40    45   50    60
 400   6.7   13.3   20   26.7   33.3    40   46.7   53.3    60   66.7    80
 500   8.3   16.7   25   33.3   41.7    50   58.3   66.7    75   83.3   100
 600   10   20   30   40   50    60   70   80    90   100   120
 700   11.7   23.3   35   46.7   58.3    70   81.7   93.3   105   116.7   140
 800   13.3   26.7   40   53.3   66.7    80   93.3   106.7   120   133.3   160
 900   15   30   45   60   75    90   105   120   135   150   180
1000   16.7   33.3   50   66.7   83.3   100   116.7   133.3   150   166.7   200
1100   18.3   36.7   55   73.3   91.7   110   128.3   146.7   165   183.3   220
1200   20   40   60   80   100   120   140   160   180   200   240
For free air:
Use equation or table

CFM x Temperature Rise (F)
3000

Use the maximum anticipated airflow. This equation assumes insulated duct (negligible heat loss) and 70F inlet air at 14.7 PSIA
For compressed air:

CFM* x Density*(lbs/cu. ft.) x Temperature rise (F)
228

*At heater inlet temperature and pressure
Note: If air flow is given in CFM at operating temperature and pressure it can be converted to SCFM (Standard Cubic Feet per Minute) with the following formula.
SCFM = CFM x ( P/14.7 ) x (530/T + 460) 
P = operating pressure (gauge pressure + 14.7)
T = operating temperature
SCFM = flow rate in CFM at standard conditions of 70F and 14.7 PSIA.
source TempcoHead1AAgif.GIF (2865 bytes)